Heat Shrinkable Terminations Upto 15 Kv Suitable For 3 Core XLPE/EPR Insulated Cable

zoom view

Kit Series: CHT-3XI, CHT-3XO

Ordering Reference

Cable Size (mm2) Kit Code (Indoor)
3 x 16 - 35 3XI - 15A
3 x 50 - 95 3XI - 15B
3 x 120 - 185 3XI - 15C
3 x 240 - 300 3XI - 15D
3 x 400 - 500 3XI - 15E
• Indoor Kit does not contain Rainshed

Cable Size (mm2) Kit Code (Outdoor)
3 x 16 - 35 3XO - 15A
3 x 50 - 95 3XO - 15B
3 x 120 - 185 3XO - 15C
3 x 240 - 300 3XO - 15D
3 x 400 - 500 3XO - 15E

Technical Specifications

Test Sequence Requirements
D.C. Voltage Withstand / 15 min 48 kV
A.C. Voltage Dry Withstand / 1 min 35 kV
Impulse Withstand 75 kV
Discharge extinction Voltage > 13 kV

Our Products

Contact Info


Quick Query